Name of product/article

281 Anti-condensation unit

Type

Zone module and collector

Anti-condensation recirculation and distribution unit, with thermostatic control of the return temperature to solid fuel generators. Brass body.
With insulation.
Female union connections.
Medium: water, glycol solutions.
Max. percentage of glycol: 50%.
Temperature range: 5–100°C.
Max. working pressure: 10 bar.
Max. recommended flow rate: 2 m3/h.
Temperature gauge scale: 0–120°C.
Anti-condensation valve
Temperature range: 5–100°C.
Settings: 45°C, 55°C, 60°C, 70°C.
Setting accuracy: ±2°C.
By-pass complete closing temperature: Tmix = Tset +10°C = Tr.